Frequently asked questions and solutions for refrigeration solenoid valves
 May 31, 2023|View:916
A, refrigeration solenoid valve does not open after the power is connected to the valve

1)The power supply voltage is too low or the power supply is not connected, the power supply and control circuit should be checked.

2) refrigeration solenoid valve coil break or burned, should replace the solenoid coil or replace the solenoid valve.

3) solenoid valve core stuck or damaged, should be disassembled, cleaning the core.

4)The main valve piston of the solenoid valve is stuck due to impurities, should be disassembled, cleaning the solenoid valve.

5) solenoid valve installed in reverse, should be reinstalled in accordance with the markings of the valve body.


refrigeration solenoid valve


Second, refrigeration solenoid valve does not close after power failure or close tightly

1) the solenoid valve core stuck, should be disassembled, clean the solenoid valve.

2) the residual magnetism in the solenoid valve sucked the core, so that it can not fall, the solenoid valve of poor quality, the solenoid valve should be replaced.

3)The core seat is not closed due to impurities, causing the solenoid valve is not closed, should clean the solenoid valve.

4) the main valve piston of the solenoid valve seat impurities, should be disassembled, cleaning the solenoid valve.

5) the main valve piston of the solenoid valve pressure spring failure, the spring should be replaced.

Third, the main valve piston on the balance hole is blocked by impurities, should be disassembled, cleaning solenoid valve

Four, refrigeration solenoid valve leakage refrigerant

1)The rubber sealing gasket between the magnetic isolation sleeve and the valve body is not properly padded, not solid, should be disassembled, replace the gasket.

2) solenoid valve in the isolation casing argon arc welding damaged and cracked, the solenoid valve should be replaced.

V. Maintenance issues worth noting

1) in the actual maintenance, refrigeration solenoid valve rarely fails. Even if there is a failure, generally due to the solenoid coil burned and caused. Compared with this, the impurities caused by the failure is relatively small.

2) After the solenoid valve coil burned, if the entire solenoid valve is replaced, the low-pressure area refrigerant must be discharged into the high-pressure area. The easy way is to put the coil of the new solenoid valve directly on the body of the old solenoid valve.

3) The rated voltage of the solenoid valve is divided into two kinds of 220V and 380V, pay attention not to mix the installation, the maintenance personnel who are not experienced enough are prone to this error.

4) In the solenoid valve re-energized state, never allow the coil from the valve body to take off. Otherwise, the coil is very easy to overheat and burned.